NAMUR solenoid valves: 3/2 or 5/2?
Choosing between a 3/2 and a 5/2 NAMUR solenoid valve depends on the pneumatic actuator it drives, single-acting or double-acting. Here is how to decide and what else to check before ordering.
On a pneumatic valve, the pilot solenoid valve looks like a small accessory. In practice, it decides how the actuator behaves when air or power is lost, and choosing the wrong version, 3/2 instead of 5/2 or the reverse, can leave an actuator inoperative or, worse, stuck in an unsafe position. Here is how to decide.
The NAMUR standard: why it makes mounting simpler
A “NAMUR” solenoid valve is not a particular valve model: it is a standardised mounting interface (defined by the VDI/VDE 3845 recommendation and adopted by NAMUR) that fixes the position and spacing of the ports on the base of the solenoid valve. This standardisation lets the solenoid valve be bolted directly onto the pneumatic actuator, with no intermediate tubing, whoever made the actuator or the solenoid valve. The practical benefits: fewer fittings, fewer potential leak points, a faster response and the ability to replace the solenoid valve without removing the actuator from the valve.
The NAMUR format comes in a 3-way / 2-position (3/2) version and a 5-way / 2-position (5/2) version. Which one you need depends entirely on the type of actuator it drives.
3/2 or 5/2: it comes down to the actuator
The 3/2 solenoid valve, for a single-acting actuator
A single-acting actuator (often called “spring-return”) has only one air chamber. Compressed air pushes in one direction, and an internal spring returns the valve to its rest position as soon as the air is cut. This naturally gives a safe position if air or power fails (closed or open depending on how it is fitted), which makes it the default choice wherever a defined fail-safe position is required.
A 3/2 solenoid valve is enough to drive this type of actuator: 1 air supply port, 1 port to the actuator chamber and 1 exhaust port. At rest, the air is cut and the chamber is vented; when energised, air fills the chamber and compresses the spring.
The 5/2 solenoid valve, for a double-acting actuator
A double-acting actuator has two chambers: air pushes alternately on one side, then the other, to open and close the valve. With no return spring, it has no rest position of its own: if the air is cut, it stays where it was.
This needs two air outlets driven at the same time in opposition, plus one supply and two exhausts: the 5-way / 2-position configuration. A 5/2 solenoid valve pressurises one chamber while venting the other, then reverses when it switches.
How to decide quickly
| Criterion | 3/2 solenoid valve | 5/2 solenoid valve |
|---|---|---|
| Compatible actuator | Single-acting (spring-return) | Double-acting |
| Safe position on failure | Set by the spring (fail-safe) | None, stays in position |
| Air ports used | 1 supply, 1 outlet, 1 exhaust | 1 supply, 2 outlets, 2 exhausts |
| Typical use | Isolation valves with a safety requirement | Process control valves with no fail-safe requirement |
The basic rule: you do not choose the solenoid valve first; you start from the actuator that is installed or specified. Fitting a 5/2 on a single-acting actuator, or the reverse, simply will not work properly, or not at all depending on how the ports are connected.
Other points to check before ordering
Beyond the 3/2 or 5/2 choice, several parameters decide whether a NAMUR solenoid valve really suits the application:
- Coil voltage (24 V DC is the most common in industrial processes, but 110/230 V AC also exists) and the type of electrical connector used on site.
- The allowable operating pressure range, to compare with the actual pressure of the compressed air network, including peaks.
- The nominal flow (Kv or Cv), which must match the volume of the actuator chambers to achieve the expected stroke time.
- The installation environment: an explosive atmosphere requires a solenoid valve certified for that risk, to be checked with the supplier before ordering, not after installation.
- Body and seal materials, especially near the sea or in salt-spray atmospheres, where corrosion degrades untreated components faster.
A component that also makes maintenance easier
Because the NAMUR interface is standardised, replacing a faulty solenoid valve needs no special tools and no actuator removal: unscrew the old one, screw on the new one, as long as the configuration (3/2 or 5/2) and the mounting pattern are the same. That is a strong argument for keeping a spare on critical lines, rather than discovering an incompatibility during an unplanned shutdown.
In short
Choosing between a 3/2 and a 5/2 NAMUR solenoid valve is not a matter of preference but a direct consequence of the actuator in place: single-acting on one side, double-acting on the other. Then checking voltage, operating pressure, flow and installation environment avoids surprises at commissioning. Nex-Parts supplies NAMUR solenoid valves and pneumatic actuators for desalination plants, mining sites and food-processing lines, in Morocco and in France. You can send a quote request through the contact form or on WhatsApp at +212 674 631 270, and we reply within 48 working hours.